Permit Number: T21CM02160
Parcel: 113061840

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM02160
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Detail WWM 401 shows both directional fittings and saddle-type fittings used to connect the HCS to a sewer main. Revise keynote 7 to note that the use of saddle-type fittings to connect an HCS to a private sewer main is prohibited. Reference: Section 707.1 (6), IPC 2018

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2021 PCAMARE1 OUT TO CUSTOMER Completed