| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/06/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Detail WWM 401 shows both directional fittings and saddle-type fittings used to connect the HCS to a sewer main. Revise keynote 7 to note that the use of saddle-type fittings to connect an HCS to a private sewer main is prohibited. Reference: Section 707.1 (6), IPC 2018 |