Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM02159
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM02159
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2021 JPEELDA1 FIRE REVIEW Approved
03/24/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/24/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/30/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The ventilation calculations indicate that the minimum required outside air flow rate for the suite is 589 CFM with a design flow rate of 300 CFM per HVAC unit but the balancing notes on the mechanical floor plan call for a total of 700 CFM for the two units. Please coordinate the notes with the calculations. Reference: Section 403.3.1.1, IMC 2018.
03/30/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/30/2021 ROBERT SHERRY WATER REVIEW Completed
04/01/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Ref; Plan sheet A1.0. Please clarify what branch circuit β€˜LI’ - 11,13 are connected to. Water Heater or Track lights. See panel schedule β€˜L1’. Correct the panel schedule if necessary.

Ref; Plan Sheet Ref 2018 IBC sec 107.2.1, 2017 NEC.
04/09/2021 SSHIELD1 ENGINEERING REVIEW Passed
04/09/2021 STEVE SHIELDS ZONING REVIEW Approved