Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM02159
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/15/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
03/24/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/24/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/30/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The ventilation calculations indicate that the minimum required outside air flow rate for the suite is 589 CFM with a design flow rate of 300 CFM per HVAC unit but the balancing notes on the mechanical floor plan call for a total of 700 CFM for the two units. Please coordinate the notes with the calculations. Reference: Section 403.3.1.1, IMC 2018. |
03/30/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
03/30/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/01/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Ref; Plan sheet A1.0. Please clarify what branch circuit βLIβ - 11,13 are connected to. Water Heater or Track lights. See panel schedule βL1β. Correct the panel schedule if necessary. Ref; Plan Sheet Ref 2018 IBC sec 107.2.1, 2017 NEC. |
04/09/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
04/09/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |