Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Is this a service upgrade to an existing service or an additional service on a existing building or structure.

Provide a site plan showing the location of the new electrical service and existing on the premises. If there is an existing electrical service(s) to remain at the building, provide compliance NEC art 230.2.

Provide TEP verified or Engineered calculated Available Fault Current at the service and show the AIC rating of all the electrical equipment.

If the fault current rating at the panel is 22K, then the circuit breakers must also be rated at 22K or provide a Engineered Series rated system.

Show the method of wiring termination at the freezer.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.