Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM01997
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/17/2021 | PCAMARE1 | ENGINEERING | REVIEW | Passed | |
| 03/23/2021 | NMARTEL1 | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL Nicholas Martell, Planner T21CM01997 Residential Addition March 23, 2021 The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed. 1. Please resubmit the plans with all setback measurements for every structure provided. 2 A permit for the existing storage on the west side of the propery was started in 2017 under permit # T17CM00101. However, the permit is in expired status. Please update your permit application and add that section of the residence to the plans with full setbacks, elevations and all other zoning requirements. If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov |
| 03/23/2021 | NMARTEL1 | NPPO | REVIEW | Passed | |
| 03/30/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Show the water pipe diameter between the meter and shut off valve in compliance with P2903.7. A minimum 1” service pipe is required for supplying water to more than 9.5 fixture units. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 |