Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM01963
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2021 | ELISA HAMBLIN | ZONING | REVIEW | Approved | Approval is for interior work only. |
| 04/14/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. All of the vents in the building shall rise vertically to at least 6” above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018. 2. Verify that the floor sinks and hand sink located along the north side of the building do not have to be connected to the grease waste system. Reference: Sections 1003.1 and 1003.3, IPC 2018 as amended by the City of Tucson. |
| 04/14/2021 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
| 04/26/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |