Permit Number: T21CM01963
Parcel: 11205283G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM01963
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2021 ELISA HAMBLIN ZONING REVIEW Approved Approval is for interior work only.
04/14/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. All of the vents in the building shall rise vertically to at least 6” above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2018.
2. Verify that the floor sinks and hand sink located along the north side of the building do not have to be connected to the grease waste system. Reference: Sections 1003.1 and 1003.3, IPC 2018 as amended by the City of Tucson.
04/14/2021 EHAMBLI1 ENGINEERING REVIEW Passed
04/26/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved