Permit Number: T21CM01941
Parcel: 13604818A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM01941
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2021 JPEELDA1 FIRE REVIEW Approved
03/23/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01941

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. S1: The roof sheathing does not meet the minimum thickness requirements of T2304.8(1).
2. S2: Concrete slab a required to have a vapor retarder located between the slab and base course per 1907.1

BUILDING REVIEW COMMENTS:
Denied
1. A1: The location of the Class K extinguisher, indicated in the architectural notes, is not shown on the plans.
2. S1: The roof sheathing does not meet the minimum thickness requirements of T2304.8(1).
3. S2: Concrete slab a required to have a vapor retarder located between the slab and base course per 1907.1

ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Approved

PLUMBING REVIEW COMMENTS:
Approved
03/24/2021 ROBERT SHERRY WATER REVIEW Completed
04/06/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM01941
8605 E Golf Links Rd.
Food Service

TRANSMITTAL: April 6, 2021
This site is located in the C-1 zone (UDC 4.7.20). Multifamily is a permitted use in this zone (Table 4.8-4).

1. Zoning has reviewed the building plans for compliance with DP21-0004 and although the building plans appear to match the DP until the DP is approved Zoning cannot approve the building plans.

2. The development package (DP) sheets provided in the building plan set either need to be the stamped approved DP sheets, marked “FOR REFERENCE ONLY”, or be removed from the building plan set.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
04/09/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change DEVELOPMENT PACKAGE MUST BE APPROVED FIRST.
04/22/2021 LBOWERS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change

Final Status

Task End Date Reviewer's Name Type of Review Description
04/22/2021 LBOWERS1 OUT TO CUSTOMER Completed