Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2021 NMARTEL1 ZONING REVIEW Approved
03/16/2021 NMARTEL1 ENGINEERING REVIEW Passed
03/16/2021 NMARTEL1 NPPO REVIEW Passed
03/24/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM01776
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on sheet A1.0. Also, update all outdated references on A6.0.

STRUCTURAL PLANS:

1. Provide a roof framing plan showing beams with appropriate load carrying capacity for live and dead loads, R801.2. The 4x8 carport beams are undersized.

SECTIONS - DETAILS:

1. Update the foundation detail references appearing on sheet A4.0, R106.1.1. These details are on A2.0.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

Please contact the plans reviewer if you have any questions: