Permit Number: T21CM01771
Parcel: 11450026A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM01771
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2021 STEVE SHIELDS ZONING REVIEW Approved
03/22/2021 SSHIELD1 NPPO REVIEW Passed
03/24/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM01771

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with code compliance.

Place each plan sheet into a single PDF file for reviewing as a complete plan set separate from support documents such as the check list and HVAC specs.

Change the code reference to the currently adopted 2018 IRC on the Site Plan.

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

PLUMBING PLANS:

Provide piping details showing code compliant materials and sizes or show relocated fixtures. Include drain and vent pipes.

MECHANICAL PLANS:

Provide equipment details showing code compliant components, locations and sizes, or show relocated components. Include exhaust fans.

ELECTRICAL PLANS:

Provide wiring details showing code compliant devices and sizes. Show circuit number and size with receptacles at all walls and lighting control at each doorway both interior and exterior. Receptacle, lighting and smoke detector circuits require arc-fault protection.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
03/30/2021 SBLOOD1 ENGINEERING REVIEW Approved