Permit Number: T21CM01756
Parcel: 126210860

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM01756
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2021 PCAMARE1 ENGINEERING REVIEW Passed
03/22/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM01756
Carport Addition
March 22, 2021
The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed. 1. Please resubmit the plans conforming to the requirements of the residential plot plan found at the following link: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf a. A full site plan with all setbacks, elevation drawings, lot coverage calculations and other plot plan standards is required.

There is an old site plan with the activity number T08CM02298 that can be used. The plans can be found at the following web address: https://www.tucsonaz.gov/pro/pdsd/permitdetail/T08CM02298/126210860. In order to make the site plan approvable, please add the information found on the template provided in the first comment.

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
03/23/2021 ANDREW CONNOR NPPO REVIEW Passed
03/24/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM01756
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site. https://www.tucsonaz.gov/pdsd/online-permits

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

GENERAL COMMENTS:

1. Items built without permit may require alteration or improvement for achieving code compliance with the 2018 IRC, R105. This cannot be determined without an evaluation by a qualified professional. Complete construction plans are required for processing a building permit. The plans should show necessary structural changes for achieving building code compliance. A 4” x 6” beam may be undersized depending on the structure dimensions and layout.

SITE PLAN:

1. Indicate the location of buildings and any utilities supporting the proposed structure.

FOUNDATION PLAN:

1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1.1.

FRAMING PLAN:

1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1.

SECTIONS - DETAILS:

1. Show the Post Section Detail with #4 rebar in the footing, R403.1.
2. Notate and specify the size and length of anchor bolts, R403.1.
3. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.
4. Show lateral support components if the carport is not attached to a building for structural stability, R802.8.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review