Permit Number: T21CM01717
Parcel: 115044030

Address:
1120 N 2ND AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM01717
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2021 PCAMARE1 ENGINEERING REVIEW Passed
03/22/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:

T21CM01717
1120 N 2nd Ave
Feldman’s NPZ,

TRANSMITTAL: March 22, 2021


COMMENTS: the following comments are relative to an application for NPZ Review (UDC 5.10.3).

This site is located in the NR-1 zone (UDC 5.10.3). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

Prior to zoning approval an NPZ review and approval is required. Owner is proposing to construct an addition and porch to the existing dwelling. The property fronts on 2nd Ave.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the building exterior wall, see UDC Article 6.4.5.B and Figure 6.4.5-A.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).
1. The proposed addition does not meet required perimeter yard setbacks to the north property line. As a dimension was not provided from design grade to the highest point of the exterior wall Zoning did a measurement using Bluebeam software, 12’-3” x 2/3 = 8’-2”, proposed perimeter yard setback to the north property line is 4’-6”.
2. The proposed porch addition does not meet required perimeter yard setbacks to the south property line. As a dimension was not provided from design grade to the highest point of the exterior wall Zoning did a measurement using Bluebeam software, 9’-9” x 2/3 = 6’-6”, proposed perimeter yard setback to the north property line is 5’-7”.

NPZ Review shall be completed and approved prior to approval of the building plans. NPZ application can be found at: https://www.tucsonaz.gov/files/pdsd/Special_Districts_Application_Revised_3-19-20_FILLABLE_PDF.pdf.



If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
03/22/2021 SSHIELD1 NPPO REVIEW Passed
03/23/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change PROVIDE A COMPLETE PLAN SET FOR REVIEW