Permit Number: T21CM01713
Parcel: 132166490

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM01713
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01713

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Denied
1-OK
2-Provide duct smoke detector as per IMC-606.2 **Not provided
3-OK
4-OK
5-OK

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
Panel B circuit 18,20 should be corrected to a 2 pole CB and the receptacle should be shown as 208 volt receptacle.
Suggest adding GFI receptacle to bathroom at plan east end of building.
Suggest to show panels as actual size. Panels shown apear to be 1/2 size.
Suggest to show Panel B on lighting sheet as well as power sheet.

PLUMBING REVIEW COMMENTS:
Denied
1-OK
2-Provide clothes washer with discharge interceptor. IPC-1003.6 **Not provided. Exception-2 only applies to clothes washers for use in individual dwelling units.
3-OK
4-Provide Facility Plumbing Fixture Calculations. IPC-Table-403.1. Provide HI/LO Drinking Fountain.**Not provided. A-8 sheet does not shows Plumbing Fixture Calculations.
5-Provide a drain pan for water heater. Show drain size, material and point of termination. IPC-504.7 **Not provided
11/19/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM01713
975 E Macarthur Cir. – I-1
New Dentist Office (2nd Review)

TRANSMITTAL: November 19, 2021
This site is located in the I-1 zone (UDC 4.7.29), Medical Service Outpatient is an allowed use in the zone (UDC Table 4.8-5), subject to Use Specific Standard 4.9.13.Q.

1. Zoning did a cursory review and it appears that the building plans match DP21-0143 but until at least one review of the DP has been completed Zoning cannot confirm. Until DP21-0143 is approved Zoning cannot approve the building plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
11/29/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change The DP needs to be approved before the building plans can be approved.

Stephen Blood
(520) 837-4958