Permit Number: T21CM01701
Parcel: 137335400

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM01701
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM01701

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Show the wall composition between the dwelling and carport for fire rating determination. The exterior dwelling wall requires 1/2” sheet rock applied over a T1-11 type wall sheathing if the wall is not a masonry product, R302.6.
2. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1.
3. Identify the room entering into the dwelling. An opening from a garage directly into a sleeping room is not permitted, R302.5.1.

If you have any questions, please contact:
Ken Van Karsen
(520) 791-5550
City of Tucson Residential Plan Review
04/19/2021 STEVE SHIELDS ZONING REVIEW Approved