Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM01661
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/15/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 2; Sheet S1.0; Detail 101: It appears this sheet has not been included in the new submittal. Please provide. 2. Previous Comment 3; Special Inspections Certificate: No Special Inspections Certificate with Parts A and B completed was included in the new submittal. Please provide. 3. General: City inspectors will not review the structural calculations for inspection issues. Please separate the set of structural calculations from the design drawings. 4. General: Please provide written responses to all review comments. |
06/22/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. The previous electrical plan review comment requesting a grounding detail and to verify compliance with NEC art 690.43A and B was not provided in the resubmittal. Please provide a grounding detail on the electrical plans. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |
07/06/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
07/06/2021 | SSHIELD1 | ENGINEERING | REVIEW | Approved |