Permit Number: T21CM01661
Parcel: Unknown

Address:
703 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM01661
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 2; Sheet S1.0; Detail 101: It appears this sheet has not been included in the new submittal. Please provide.
2. Previous Comment 3; Special Inspections Certificate: No Special Inspections Certificate with Parts A and B completed was included in the new submittal. Please provide.
3. General: City inspectors will not review the structural calculations for inspection issues. Please separate the set of structural calculations from the design drawings.
4. General: Please provide written responses to all review comments.
06/22/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

The previous electrical plan review comment requesting a grounding detail and to verify compliance with NEC art 690.43A and B was not provided in the resubmittal. Please provide a grounding detail on the electrical plans.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.
07/06/2021 STEVE SHIELDS ZONING REVIEW Approved
07/06/2021 SSHIELD1 ENGINEERING REVIEW Approved