Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM01619
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheets A1.0, A2.0, A3.0, and D1.0: All drawings must be sealed, signed, and dated by a registered design professional for commercial projects. Please provide. |
| 04/29/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Please clarify the previous electrical plan review comment; It appears that System #1 and System #2 projects T21CM01619 AND T21CM01620 are assigned to the same electrical service, please verify. If that’s the case, adjustments will have to be made to the electrical design to meet Code requirements. NEC art. 690 and 705.12B(2). Or if not, then please identify each electrical service on the plans with an address or building identification. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |