Permit Number: T21CM01605
Parcel: 13216600A

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM01605
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2021 JPEELDA1 FIRE REVIEW Approved
03/17/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Ref; Plan Sheet E2.1. The line diagram shows the new compressor #3 feeder connected to a 500 amp OCPD. The Conduit and Feeder schedule on plan sheet E3.2C shows the feeder sized at 3-500 MCM and a 4/0 ground. The amp rating of the conductors is inadequate for the rating of the OCPD protecting this feeder per NEC 240.4 and Table 310.15(B)(16). Please clarify.

Ref 2018 IBC sec 107.2.1, 2017 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2021 IMONSHI1 OUT TO CUSTOMER Completed