Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM01605
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/11/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
03/17/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
03/23/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Ref; Plan Sheet E2.1. The line diagram shows the new compressor #3 feeder connected to a 500 amp OCPD. The Conduit and Feeder schedule on plan sheet E3.2C shows the feeder sized at 3-500 MCM and a 4/0 ground. The amp rating of the conductors is inadequate for the rating of the OCPD protecting this feeder per NEC 240.4 and Table 310.15(B)(16). Please clarify. Ref 2018 IBC sec 107.2.1, 2017 NEC. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/24/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |