Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T21CM01605
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 03/17/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/23/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Ref; Plan Sheet E2.1. The line diagram shows the new compressor #3 feeder connected to a 500 amp OCPD. The Conduit and Feeder schedule on plan sheet E3.2C shows the feeder sized at 3-500 MCM and a 4/0 ground. The amp rating of the conductors is inadequate for the rating of the OCPD protecting this feeder per NEC 240.4 and Table 310.15(B)(16). Please clarify. Ref 2018 IBC sec 107.2.1, 2017 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/24/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |