Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM01599
Parcel: 133091100

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM01599
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/20/2021 ROBERT SHERRY WATER REVIEW Completed
07/20/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. COMcheck for the building envelope has not been submitted, only the mechanical COMcheck. [Second comment: Provide the COMcheck Envelope Compliance certificate.] [Initial comment: Alterations of an existing, non-conditioned building shall be brought into full compliance with the 2018 International Energy Conservation Code. Demonstrate energy code compliance for the building envelope, mechanical systems, and interior lighting using calculations based on the current code (e.g. COMcheck). Reference: Section C503.2, IECC 2018.]
2. A 10% increase over an 11.50 EER is 12.65, not 12.30. [Second comment: High efficiency unitary and applied heat pumps with a cooling capacity that is less than 65MBH must have a SEER 10% greater than the minimum SEER of 14. (Alternatively, you could use reduced lighting power as your additional efficiency option – the lighting design already complies with that requirement.)] [Initial comment: Show how one of the “Additional Efficiency Package Options” (C406, IECC 2018) is to be accomplished. Reference: Section C401.2, IECC 2018.]