Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM01590
Parcel: 105102680

Address:
4282 N 1ST AV

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM01590
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/23/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2021 IMONSHI1 OUT TO CUSTOMER Completed