Permit Number: T21CM01587
Parcel: 126040380

Address:
4455 E 4TH ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM01587
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM01587

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with code compliance.

Place each plan sheet into a single PDF file for reviewing as a complete plan set.

Use the Residential Plan Requirements & Checklist at https://www.tucsonaz.gov/pdsd/residential-permits

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide a complete site plan showing all buildings and utility lines, R106.1.1. Show setback measurements to property lines and location of utility lines to the building.

FLOOR PLAN:

Provide a floor plan showing the proposed future building. Show door locations and window sizes with type identified as XO or SH. .

ELEVATION SECTION:

Provide each elevation showing the building height. This may affect set back requirements

SECTIONS - DETAILS:

1. Framed exterior walls of enclosed roof structures require continuous concrete footings of minimum 12” width and 12” below the undisturbed ground surface, R403.1.
2. Locate and specify all anchor-bolt spacing on the foundation plan. Minimum ½” diameter with (anchor bolt length for assuring) 7” embedment into concrete or masonry, R403.1.6. Maximum spacing 6’ o/c and within 12” of each sill plate end, R403.1.6.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
04/23/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21CM01587
4455 E 4th St
Foundation only for detached shed 12’ x 20’ (1st Review)

TRANSMITTAL DATE:

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

1. Provide a plot plan the meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. Ensure that exterior wall heights are provided so that perimeter yard setbacks can be verified.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2021 PCAMARE1 OUT TO CUSTOMER Completed