Permit Number: T21CM01550
Parcel: 30501001A

Address:
10200 S RITA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM01550
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Please provide total load calculation for the loads served by this Service. Include this on the line diagram plan.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.