Permit Number: T21CM01550
Parcel: 30501001A

Address:
10200 S RITA RD

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM01550
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/24/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide a complete electrical line diagram. Include:

(a) AIC Ratings of the electrical service and downstream equipment.

(b) Provide a Grounding detail for the Transformers and Service.

(c)Indicate whether the feeder to Customer Equipment is new or existing, and show conduit, conductor quantities, sizes and types.



Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/25/2021 IMONSHI1 OUT TO CUSTOMER Completed