| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/24/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide a complete electrical line diagram. Include: (a) AIC Ratings of the electrical service and downstream equipment. (b) Provide a Grounding detail for the Transformers and Service. (c)Indicate whether the feeder to Customer Equipment is new or existing, and show conduit, conductor quantities, sizes and types. Ref; 2018 IBC 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/25/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |