Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM01548
Parcel: 107130800

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM01548
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM01480, T21CM01542, T21CM01543, T21CM01544, T21CM01545, T21CM01546, T21CM01547, T21CM01548
263 W Glenn St
Multi-family

TRANSMITTAL: March 8, 2021
This site is located in the R-3 zone (UDC 4.7.12). Food Service is an approved use in the zone (Table 4.8-2) subject to Use Specific Standard 4.9.7.B.6.

1. The building plan has been reviewed for compliance with DP21-0038 and although it appears that they comply until the DP is approved Zoning cannot approve the building plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
03/08/2021 SSHIELD1 NPPO REVIEW Passed
03/17/2021 PCAMARE1 ENGINEERING REVIEW Reqs Change FROM: Paul Camarena
PDSD Engineering Review Section

PROJECT: T21CM01548
263 W GLENN ST

TRANSMITTAL DATE: March 17, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Engineering Review Section comments were addressed.

01. COMMENT: Engineering has reviewed the plan and cannot approve at this time. Please address the following comments.


02. COMMENT: Engineering cannot approve until Development Package is approved.





If you have any questions about this transmittal, Contact Paul Camarena at Paul.Camarena@tucsonaz.gov
03/17/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM01480, 1542-48
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Remove the “PREPLIMINARY” notation from sheets S2, S3 & S5.
2. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide gray water utilization or preparation, Ordinance #10579/11089 revised July 9, 2013. Property with 200 to 400 SF of available distribution area requires piping for one gray water fixture, and a property with over 400 SF requires complete compliance. Include two clothes washer standpipes, one with an above grade stub-out, and one to the building drain; also provide gray drain-line discharge of all second story bathing fixtures through an exterior-wall drop for future gravity distribution or, notate “Gray water provision not required only when property has less than 200 SF available for gray water distribution.”

SITE PLAN:

1. Provide a street address, R319.1.

FLOOR PLANS:

1. Show a maximum ½” floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1. Include the threshold condition at the doorway for the accessible route.

SECTIONS - DETAILS:

1. Show one-hour rated construction at Detail 201 & 204 consistent with sheet A2, R302.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review