Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM01489
Parcel: 11918038D

Address:
3665 S 16TH AV

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM01489
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. A sanitary floor drain (P-1) installed upstream of the sanitary floor drain serving E-6 does not show a plumbing fixture or appliance draining into it. Verify that the plumbing fixture or appliance draining into it does not need to discharge to the grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
2. Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.9, IPC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2021 IMONSHI1 OUT TO CUSTOMER Completed