Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/06/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. A sanitary floor drain (P-1) installed upstream of the sanitary floor drain serving E-6 does not show a plumbing fixture or appliance draining into it. Verify that the plumbing fixture or appliance draining into it does not need to discharge to the grease interceptor. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson. 2. Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.9, IPC 2018. |