Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM01474
Parcel: 12409156A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM01474
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2021 DTRAMME1 ENGINEERING REVIEW Passed
03/03/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/03/2021 JPEELDA1 FIRE REVIEW Approved
03/18/2021 ROBERT SHERRY WATER REVIEW Completed
03/24/2021 STEVE SHIELDS ZONING REVIEW Approved
04/01/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01474

GENERAL:
1. Provide written responses to all review comments.
2. Provide a complete plan set.
3. Provide additional documents as requested by review staff.
STRUCTURAL REVIEW COMMENTS:
N/A

BUILDING REVIEW COMMENTS:
Andrew Bevis
Denied
Reason:
Date Completed : 3/28/2021

1. The occupant loads are calculated incorrectly. Since there is adequate exiting off the patio area, the outside patio area would not be required to be calculated and would not affect any other code requirements throughout the project.
2. The occupant load for the seating area is calculated incorrectly. This should be calculated at 15 net per Table 1004.5.
3. Exit access are not permitted to pass through storage rooms per Section 1016.2 #5.

ELECTRICAL REVIEW COMMENTS:
Andrew Bevis
Approved
Reason:
Date Completed : 3/28/2021

MECHANICAL REVIEW COMMENTS:
Andrew Bevis
Approved
Reason:
Date Completed : 3/28/2021

PLUMBING REVIEW COMMENTS:
Andrew Bevis
Approved
Reason:
Date Completed : 3/28/2021