Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM01468
Parcel: 110113620

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM01468
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2021 DTRAMME1 ENGINEERING REVIEW Passed
03/03/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/03/2021 JPEELDA1 FIRE REVIEW Approved
03/18/2021 ROBERT SHERRY WATER REVIEW Completed
03/24/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01468

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
N/A

BUILDING REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
1. Provide a passing comcheck

MECHANICAL REVIEW COMMENTS:
Denied
1. Provide a passing comcheck

PLUMBING REVIEW COMMENTS:
Approved
03/24/2021 STEVE SHIELDS ZONING REVIEW Approved