Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM01404
Parcel: 140152980

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T21CM01404
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2021 PIMA COUNTY BUILDING-RESIDENTIAL REVIEW Passed
03/30/2021 STEVE SHIELDS ZONING REVIEW Approved
03/30/2021 SSHIELD1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/31/2021 IMONSHI1 OUT TO CUSTOMER Completed