Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM01312
Parcel: 122173090

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM01312
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01303, T21CM01312

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
The following comments from Submittal 1 are not addressed, address these items and resubmit.
Building 1
5) S2.1: Provide information about the thickness and reinforcing of the concrete slab on grade. show control joints (saw-cut), lay-out
6) S2.1: Please label the continuous wall footings at grids 4,5 & 6 between A&E grids.
7) S2.1: Show footing on grid 2A.
8) S2.2: At unit B there is a B-9 (2)2x12 beam at 2nd level located between E&F grids. Both end reactions of this beam receives loads from the levels above and loads the edge of interior bearing wall. Check the end studs of the opening . You may need a wood post or multiple studs to support the concentrated load.
9) S2.3; At third level of unit B there is a beam between Grids E & F which is not labelled.
10) See A3.0 /Detail 8; provide information for the tube steel frame member size and its welded connections ,including corrugated sheet attachment.
11) S4.1; At section 9 ;specify the distance between grade and top of footing.
12) S2.4: Show roof top units on roof framing plan including equipment platform.
13) S2.4: Section mark on grid J cut thru B-11 Beam needs to be labelled.
14) Provide a typical section at balconies of the 2nd and 3rd level.

Building 2
15) S3.1: At Foundation plan ;show saw-cut layout.
16) S3.2: Show roof top units on roof framing plan.
17) Both buildings : provide a wind design calculation as per ASCE 7-16/section 29.4.1 and detail the connection between the unit and curb and also between the curb and roof framing. Detail the opening at unit location. ( Make calculation and detail for the worst condition only.
18) Please respond in writing. Provide a brief narrative for the revisions.

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approval Pending


PLUMBING REVIEW COMMENTS:
Approved
12/15/2021 ROBERT SHERRY WATER REVIEW Reqs Change Comment not resolved. A site plan that is for "informational purposes only" can't be used to construct the building sewers, the gas service, and the water service to the buildings. Provide a plan that can be used to construct the on-site utilities. [Second comment: An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide the civil plans showing the installation of the water service to the building and the installation of the building sewer as part of the building plan set. Reference: Sections 107.2.1 and 107.2.6, IBC 2018 [Initial comment: Show the location and size of the proposed water meter, backflow preventer, and the water service pipe on a site plan. The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.]
12/17/2021 STEVE SHIELDS ZONING REVIEW Approved