Permit Number: T21CM01302
Parcel: 13316024M

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM01302
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2021 DTRAMME1 ENGINEERING REVIEW Passed
03/03/2021 JPEELDA1 FIRE REVIEW Approved
03/16/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/16/2021 STEVE SHIELDS ZONING REVIEW Approved
03/16/2021 ROBERT SHERRY WATER REVIEW Completed
04/07/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01302

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. Provide an emergency egress plan that provides travel distances and paths to all exits.
2. Sheet A1: The sames counter is requierd to ahve an accessible portion in compliance with Section 227.3 of the ADA guidelines and Section 904 of A117.1 (2009)
3. Sheet A4: The sink provided in the break room is required to be accessible in compliance of 804.4 of the ADA guidelines and Section 606 of A117.1 (2009)

ELECTRICAL REVIEW COMMENTS
Denied
E3: Detail 1: Service entrance calculations show Panel 110 with 59809 amps when it is supposed to be 167 amps. Correct ampacity value.

MECHANICAL REVIEW COMMENTS:
Approved

PLUMBING REVIEW COMMENTS:
Approved