Permit Number: T21CM01290
Parcel: 13502024A

Address:
6470 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM01290
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2021 DTRAMME1 ENGINEERING REVIEW Passed
03/03/2021 JPEELDA1 FIRE REVIEW Approved
03/15/2021 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/15/2021 STEVE SHIELDS ZONING REVIEW Approved
03/15/2021 ROBERT SHERRY WATER REVIEW Completed
03/16/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM01290

GENERAL:
1. Provide written responses to all review comments.
2. Provide a complete plan set.
3. Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Andrew Bevis
Approved
Reason:
Date Completed : 3/10/2021 1:29:35 AM

BUILDING REVIEW COMMENTS:
Andrew Bevis
Approval Pending
Reason:
Date Completed : 3/10/2021 1:49:39 AM

1. Ensure proper amount of accessible seating in the dining area.

ELECTRICAL REVIEW COMMENTS
Ron Ross
Denied

Reason:
Date Completed : 3/15/2021 9:31:12 PM Electrical Review
By Ron Ross PE

1. E1 RCP/LIGHTING PLAN: Plans are signed and seal by an Architect, not an engineer. Confirm that an Architect can sign drawings.

2. E2 ELECTRICAL FLOOR PLAN: No electrical comments

3. E3 ELECTRICAL NOTES – PANEL SCHEDULE: Existing Service is 240/120 V single phase. Panel is 3 phase and will not be a code compliant installation. Service or panel needs to be corrected. This error may require the set to be prepared and signed by an electrical PE.


MECHANICAL REVIEW COMMENTS:
Andrew Bevis
Approved
Reason:
Date Completed : 3/11/2021 12:37:52 AM


PLUMBING REVIEW COMMENTS:
Andrew Bevis
Approved
Reason:
Date Completed : 3/11/2021 12:39:07 AM