Permit Number: T21CM01285
Parcel: 121121120

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM01285
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2021 SBLOOD1 ENGINEERING REVIEW Passed
03/03/2021 STEVE SHIELDS ZONING REVIEW Approved
03/03/2021 ANDREW CONNOR NPPO REVIEW Passed
03/11/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM01285
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL PLANS:

1. Provide rafter sizes and spacing in compliance with Table R802.4. A correction may be obtained from a registered structural engineer.

PLUMBING PLANS:

1. Clarify the water pipe diameter between the meter and shut off valve in compliance with P2903.7. A minimum 1” service pipe is required for supplying water to more than 9.5 fixture units.

MECHANICAL PLANS:

1. Show combustion air compliance for appliances in confined spaces with a minimum of one exterior area opening of 1 SQ IN for each 3,000 BTU rating terminating within 12” of enclosure top and with clearance of 1” sides and back and 6” from front of the appliance, G2407.6.2. Two exterior openings may be shown per G2407.6.1.