Permit Number: T21CM01283
Parcel: 117200270

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T21CM01283
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change A complete set of drawings must be included in the second submittal.
05/12/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a complete drawing set for approval.
05/12/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Could not locate 2012 Outdoor Lighting Code compliance calculations in the resubmittal as requested in the previous electrical plan review comments.
05/12/2021 JPEELDA1 FIRE REVIEW Approved
05/12/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a complete drawing set for approval.
05/12/2021 ROBERT SHERRY WATER REVIEW Approved
05/13/2021 MGAYOSS1 DESIGN PROFESSIONAL REVIEW Reqs Change 5/13/2021
RNA COMPLIANCE REVIEW OF CDs DATED 2021/02/10
BY MARIA GAYOSSO
1. On Sheet A212 (PDF electronic page 11), please revise the elevations to match the elevations and materials approved through the RNA review process on 11/23/2020, under T20SA00320(RNA-DRB-20-07 / HPZ-20-073). Also, please label materials on the elevation drawings.
05/17/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM01283
260 S Church Ave
TCC – West Meeting Rooms

TRANSMITTAL: May 17, 2021
This site is located within PAD-1

1. Zoning has reviewed the building plans for compliance with DP20-0205 and although the building plans appear to match the DP until the building plans have been approved by the Design Professional Zoning cannot approve the building plans.

2. DP20-0205 will need to be issued prior to issue of this building plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
05/19/2021 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed