Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T21CM01283
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/03/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G111; Lower Level Life Safety Plan: Should the double door at the east wall (north of Storage Room 114) indicate "No Exit" signage on this plan? Please verify. 2. Sheets G111 and G112; Code Analysis: Please provide plumbing fixture requirement calculations on the drawings for the addition. Indicate if fixtures in the existing building are to be considered for this addition. If so, verify the requirements of the IBC Section 2902.3.3 are met. 3. Sheet S1.0; Structural Notes (Foundations): The first note indicates a soil report was used for the foundation design. Please provide that report for review. 4. Sheets A101 and A111; Floor Plans: Please add a note on these sheets to reference Sheet A314 for Wall Types. 5. Sheet A314 (Wall Schedule); Sheet S1.7 (Typical CMU Wall Reinforcement Schedule): Wall Types B, E, K, and N indicate 8" CMU vertical reinforcing at 48" o.c., while the Typical CMU Wall Reinforcement Schedule indicates typical 8" CMU walls have #5 verticals at 32" o.c.. Please coordinate. 6. General: Please provide the Special Inspections Certificate with Parts A and B completed. 7. General: Please provide written responses to all review comments. |
03/04/2021 | SBLOOD1 | ENGINEERING | REVIEW | Approved | |
03/04/2021 | JPEELDA1 | FIRE | REVIEW | Reqs Change | 1. Sheet G111; Lower Level Life Safety Plan: Should the double door at the east wall (north of Storage Room 114) indicate "No Exit" signage on this plan? Please verify. 2. Please reference the IFC that will be applied on sheet G111 |
03/10/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the water calculation on sheet P601: what is the source of the 50 PSI static pressure? Reference: Section 107.2.1, IBC 2018. 2. Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks (e.g. the 2” waste from the mezzanine lavatories and the 4” waste from rooms 206A and 207A) . Reference: Section 704.3, IPC 2018. 3. Provide roof drainage calculations. Show how overflow protection has been provided for all sections of the roof. Show the slope of the horizontal rainwater pipes on the plans. If an overflow is not to be installed, provide structural calculations to show that the roof can support the weight of water that will accumulate if the primary roof drain is blocked. Reference: Sections 1101, 1106 and 1108, IPC 2018 and Section 1611.1, IBC 2018. 4. Primary rainwater leaders may not discharge onto a sidewalk. Show how the two 6” primary roof drain leaders will not cause drainage across the new pedestrian walkway on the west side of the addition. Reference: Section 7-01.4.1 E, Technical Standards Manual, Tucson Arizona Unified Development Code. |
03/10/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. 2. Provide complete compliance with the 2018 IECC for the lighting.3. Provide CFI protection for the drinking fountain power.NEC 422.5. 4. Provide compliance with NEC art 210.71 for meeting room receptacle outlets placement. |
03/10/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide the size of the water meter serving this addition, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. 2. Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018. |
03/10/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide smoke detectors in the return air ducts, upstream of any outside air connections, for RTU-1 and RTU-2. Reference: Section 606.2.1, IMC 2018, as amended by the City of Tucson. 2. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Sections C103.2, C303, and C502.1, International Energy Conservation Code 2018. 3. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. |
03/16/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM01283 260 S Church Ave TCC – West Meeting Rooms TRANSMITTAL: March 16, 2021 This site is located within PAD-1 1. Zoning has reviewed the building plans for compliance with DP20-0205 and although the building plans appear to match the DP until the building plans have been approved by the Design Professional Zoning cannot approve the building plans. 2. DP20-0205 will need to be issued prior to issue of this building plan. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov. |
04/19/2021 | LBOWERS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Reqs Change |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/19/2021 | LBOWERS1 | OUT TO CUSTOMER | Completed |