Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T21CM01212
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2021 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 02/24/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/24/2021 | SSHIELD1 | NPPO | REVIEW | Passed | |
| 03/10/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T21CM01212 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. FLOOR PLANS: 1. Show the door from a garage to laundry room with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1. STRUCTURAL PLANS: 1. Show braced wall panel compliance for framed walls with a garage door opening, Table R602.10.5. For prescriptive braced wall structures show a portal frame with hold-downs PFH method, Figure R602.10.6.2, or a portal frame at garage door PFG method, Figure R602.10.6.3, or a continuously sheathed portal frame CS-PF method, Figure R602.10.6.4. 2. Provide a complete roof framing plan to include the laundry room, R802.3. SECTIONS - DETAILS: 1. Clarify the placement of laundry room ceiling/roof insulation for determining the need for attic ventilation, R806. 2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. MECHANICAL PLANS: 1. Show impact protection for appliances located in the garage, M1307.3.1. 2. Show dryer vent size and location for venting to exterior, M1501. ELECTRICAL PLANS: 1. Clothes Washer GFCI: receptacles require a readily accessible protection device, E3902.9 & 10. Add notation to plans. 2. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |