Permit Number: T21CM01204
Parcel: 115211570

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM01204
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2021 ALEXANDRA HINES ZONING REVIEW Approved
04/19/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S2.0 (Array P1 Profile); Structural Calculations (Page 16): The calculations indicate a W12x50 girder beam, while the Profile indicates a W12x45. Please coordinate.
04/22/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Provide a complete panel schedule for panel ā€˜C’ include load calculations for the added EV chargers and canopy lighting.

Provide a wiring detail showing the proposed wiring methods and local disconnecting means for the new canopy lighting and. NEC 225.31, 32.

Please update the plans and re-submit.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements.