| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/07/2021 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 04/19/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S2.0 (Array P1 Profile); Structural Calculations (Page 16): The calculations indicate a W12x50 girder beam, while the Profile indicates a W12x45. Please coordinate. |
| 04/22/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Provide a complete panel schedule for panel āCā include load calculations for the added EV chargers and canopy lighting. Provide a wiring detail showing the proposed wiring methods and local disconnecting means for the new canopy lighting and. NEC 225.31, 32. Please update the plans and re-submit. Ref; 2018 IBC sec 107.2.1, 2017 NEC, City of Tucson Commercial Permit/Plan Submittal Requirements. |