Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM01073
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/25/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | 1. Provide occupant load calculation for industrial occupancy per 2018 IBC T1004.5. 4. Existing door hardware must not require special knowledge per 2018 IBC 1010.1.9. 3. Portable fire extinguishers must be installed every 75 feet per 2018 IBC (F)T906.3(1). 7. Existing tenant separation enclosed openings must be 2-hour rating per 2018 IBC T508.4. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 |
01/25/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T21CM01073 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. BUILDING REVIEW COMMENTS: Denied 1. Provide occupant load calculation for industrial occupancy per 2018 IBC T1004.5. 4. Existing door hardware must not require special knowledge per 2018 IBC 1010.1.9. 3. Portable fire extinguishers must be installed every 75 feet per 2018 IBC (F)T906.3(1). 7. Existing tenant separation enclosed openings must be 2-hour rating per 2018 IBC T508.4. 12. Restroom walls and floor must be smooth, hard, and nonabsorbent per 2018 IBC (P)1209.2. 16. Provide new exterior hot water heater enclosure construction details per 2018 IBC 107.2. 17. Show existing electrical panel size, circuits, wires, and load summary per 2018 IBC 107.3. MECHANICAL REVIEW COMMENTS: Denied 1. Show existing and new roof top vent locations and proper clearances per 2018 IMC 801. 2. 2. Provide new ductless heat pump unit exterior case location and details per 2018 IMC 302. 3. 3. Show new equipment vent support locations and construction details per 2018 IMC 802. PLUMBING REVIEW COMMENTS: Denied 1. Show gas piping inspection, testing and purging construction details per 2018 IGC 406. 2. 2. Provide fire partition locations and new piping through wall repair details per 2018 IBC 107.2. 3. 3. Show new gas equipment combustion, ventilation, and dilution air details per 2018 IGC 304. |
02/01/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved |