Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T21CM01073
Parcel: Unknown

Address:
505 E 9TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM01073
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2021 ROBERT SHERRY WATER REVIEW Completed
02/25/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/25/2021 DTRAMME1 ENGINEERING REVIEW Passed
02/25/2021 JPEELDA1 FIRE REVIEW Reqs Change Plans shall show the applicable codes.
Plans shall show the occupant load
Plans shall show the square footage
Plans shall show the egress plans
03/09/2021 STEVE SHIELDS ZONING REVIEW Denied ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM01073
505 E 9th St.
TI - Perishable Goods Manufacturing

TRANSMITTAL: March 9, 2021
This site is located in the C-3 zone (UDC 4.7.22). Perishable Goods Manufacturing is not an allowed use in the zone (Table 4.8-4).

1. Perishable Goods Manufacturing is not an allowed primary use in the C-3 zone. A rezoning is required. At best the propose use is allowed as an accessory use limited to 33% of the gross floor area of the primary use.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
03/10/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change GENERAL: Please provide written responses to all review comments

BUILDING:
Scott Davis
Denied
Reason:
Date Completed : 3/9/2021

1. Submit a life safety plan showing all materials and equipment locations per 2018 IBC 107.2.
2. Submit entire COMcheck mechanical compliance certificate checklist per 2018 IEC C501.
3. Show existing or new fire systems locations and construction details per 2018 IBC 107.2.
4. Provide existing and new door types, sizes, and hardware schedule per 2018 IBC 107.3.
5. Show existing or new handicap accessibility restrooms and details per 2009 ICC A117.1.
6. Provide existing and new parking space location and construction details per site plan.
7. Show existing occupancies and fire separation locations and details per 2018 IBC 508.4.
8. Provide building type of construction and square footage information per 2018 IBC 506.2.
9. Show existing or new emergency exit illumination and exit sign locations per 2018 IBC 1008.
10. Provide existing or new exterior walls and roof insulation information per 2018 IEC C501.
11. Show existing or new restroom door enclosing fixtures to ensure privacy per 2018 IBC 1209.
12. Provide restroom floor, walls and partition nonabsorbent surface details per 2018 IBC 1209.
13. Show existing or new handicap accessibility route location and details per 2009 ICC A117.1.
14. Provide existing roof material locations and construction specifications per 2018 IBC 1507.
15. Show existing masonry walls construction details and specifications per 2018 IBC 1404.
16. Provide new exterior hot water heater enclosure construction details per 2018 IBC 107.2.
17. Show existing electrical panel size, circuits, wires, and load summary per 2018 IBC 107.3.

ELECTRICAL:
Passed

MECHANICAL:
Scott Davis
Denied
Reason:
Date Completed : 3/9/2021

1. Show existing and new roof top vent locations and proper clearances per 2018 IMC 801.
2. Provide new ductless heat pump unit exterior case location and details per 2018 IMC 302. 3.
3. Show new equipment vent support locations and construction details per 2018 IMC 802.

PLUMBING:
Scott Davis
Denied
Reason:
Date Completed : 3/9/2021

1. Show gas piping inspection, testing and purging construction details per 2018 IGC 406.
2. Provide fire partition locations and new piping through wall repair details per 2018 IBC 107.2. 3.
3. Show new gas equipment combustion, ventilation, and dilution air details per 2018 IGC 304.