Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM01027
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 02/22/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 02/23/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/23/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet g1.1; Code Analysis: The Occupant Load for the First Floor indicates 7853 SF with 79 Occupants. Does this SF and Occupant Load include the new TI area of 1380 SF with 10 Occupants? Please clarify. 2. Sheet g1.1; Code Analysis; Exiting Plan: The Exiting Plan indicates an existing TI with 52 Occupants and the new TI with 20 Occupants for a total of 72 Occupants on the First Floor. The Code Analysis indicates the new TI with 10 Occupants. Please coordinate. 3. Sheet g1.1; Exiting Plan: The Exiting Plan indicates 36 Occupants at the north exit and 26 Occupants at the south exit for a total of 62 Occupants. Please coordinate with the Code Analysis. 4. Sheet a9.0; Partition Schedule: Please indicate the wall stud gauge and spacing for the various Partition Types. 5. General: Please provide written responses to all review comments. |
| 02/24/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 02/24/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/24/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/02/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/04/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |