Permit Number: T21CM00904
Parcel: 125076560

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00904
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2021 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/23/2021 STEVE SHIELDS ZONING REVIEW Approved
02/23/2021 JVINCEN1 FIRE REVIEW Approved
02/23/2021 DTRAMME1 ENGINEERING REVIEW Passed
04/09/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM00904

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. Revise plans to include site plan. Grease interceptor location and details. Accessible parking spaces and details. IBC
107.1 ANSI 117.1 IBC 1104.1
2. Revise plans to include scope of work. IBC 107.1
3. Revise plans to include demo plan. IBC 107.1
4. Revise plans to show accessible path of travel from accessible parking to primary building entrance. ANSI 117.1
5. Revise plans indicating exit sign locations and electrical to sign details. IBC 1013.1
6. Revise plans indicating which dining surfaces for the seating and standing spaces will be accessible. IBC 1106.2.9.1
7. Revise plans indicating restroom door signage details. ANSI 117.1
8. Revise plans to include window schedule if any new windows are being installed. IBC 107.1
9. Revise plumbing plan to include grease trap sizing and statement existing grease trap sized appropriately for new
restaurant. IPC1003

ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Approved

PLUMBING REVIEW COMMENTS:
Approved