Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM00864
Parcel: 132130770

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T21CM00864
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T21CM00864

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
N/A


BUILDING REVIEW COMMENTS:
N/A


MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
ep701: Need to provide conductor size for wire and conduit size for #13 which is used by Panels 1LV1 and 1LV3.

PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/12/2022 VVERA1 OUT TO CUSTOMER Completed