Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T21CM00864
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM00864 REV3 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: N/A BUILDING REVIEW COMMENTS: N/A MECHANICAL REVIEW COMMENTS: Denied 1-If Hotel has more than 50 guess rooms, then provide Card Key Controls complying with 2018 FECC-C403.7.6.1 and C403.7.6.2 ELECTRICAL REVIEW COMMENTS Conditionally Approved ep701: Need to provide conductor size for wire and conduit size for #13 which is used by Panels 1LV1 and 1LV3. PLUMBING REVIEW COMMENTS: Denied 1-Provide floor drain FD1 with trap and trap seal protection to comply with 2018 IPC-1002.1 (or note on plans applicable exception) and 1002.4.1. Coordinate information between Plumbing Fixture Schedule on P3.0 sheet and Soil Vent Riser on P3.0 sheet. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/07/2022 | VVERA1 | OUT TO CUSTOMER | Completed |