Review Details: REVISION - - 1ST

Permit Number - T21CM00864
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Electrical
Approval Pending

Drawing set not in same order as drawing legend.
E001 electrical notes, symbols, abbreviations, and light fixture schedule: Not in sheet legend.
ep601 panel schedule: Suggest to upsize CBs for PTAC units from 20A to 30A.
ep603 panel schedule: Suggest to upsize CBs for PTAC units from 20A to 30A.
ep604 panel schedule: Suggest to upsize wire and CBs for PTAC units for panel 2LV4. Suggest to upsize CBs for other
panel PTAC units.
ep605 panel schedule: Suggest to upsize CBs for PTAC units from 20A to 30A.
ep606 panel schedule: Suggest to upsize wire and CBs for PTAC units for panel 3LV4 and 3LV5.
ep607 panel schedule: Suggest to upsize CBs for PTAC units from 20A to 30A.
ep608 panel schedule: Suggest to upsize wire and CBs for PTAC units for panels.