Permit Number: T21CM00795
Parcel: 132131210

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM00795
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2021 JPEELDA1 FIRE REVIEW Approved
02/23/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM00795
3434 S Kino PW
New Food Service

TRANSMITTAL: February 22, 2021
This site is located in the PAD-15. Food Service is a permitted use in this zone.

1. Zoning has reviewed the building plans for compliance with DP21-0019 and although it appears that the building plans match the DP the building plans cannot be approve until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
03/02/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change Sheet 1
1. Zoning C-2 does not match DP zoning PAD-15. Please revise accordingly.
2. Approval of the Development Package is required before this plan set may be approved.
Sheet 4 (AS.1)
1. Match Lot 4 SF as shown in Development Package.
Sheet 5 (AS.2)
1. Keynote 35 indicates bicycle parking adjacent to dumpster that is not shown on DP. DP shows bicycle parking where this plan shows outdoor patio seating. Please revise accordingly.
2. Clarify that Keynote 43 if seating is for eating or waiting. Project scope states there is no patio area designated for eating/drinking.
Sheet 6 (AS.3)
1. Detail 7 needs the 60" min dimension to match the 7' clearance shown in the DP Detail B.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
03/15/2021 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
04/05/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM00795

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Structural steel, components and fasteners that are exposed need to be protected against corrosion in accordance with
AISC 360 Section B.13 as indicated in IBC 2018 Section 2203.1.
2. Designer is to coordinate venting and drainage hole requirements for HSS tube members that are galvanized using the
hot-dip galvanizing process. Provide for plugs as needed.
AWS D-19.0 calls for welds on galvanized steel to be free of zinc. Field welds on galvanized parts requires the removal of the
zinc coating in the area of weld. Provide zinc paint (approved by the galvanizer) and apply as required to the weld and steel
area to provide protection.
3. Roof drainage and secondary drains are to comply with IBC 1502.1.
4. A Section 305/S602 is shown on Roof Plan (Drg S301) near Line A and 4. Verify and make revisions.
5. Locate Section 307 shown on Drg S601 on Roof Plan S301.Denied

BUILDING REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

MECHANICAL REVIEW COMMENTS:
Approved

PLUMBING REVIEW COMMENTS:
Denied
Where: DFU = Drainage Fixture Units per Table defined in Pima County Industrial Wastewater Ordinance 13.36.420 (C) •
The minimum retention time of 30 minutes is based on Wastewater Engineering, Treatment, Disposal and Reuse, Third
Edition, Metcalf and Eddy, Inc., McGraw-Hill, Inc., page 1028. • A minimum of 25% storage is required for floatable fats, oil
and grease and settled solids is required for gravity grease interceptors. • The minimum sized GGI to be installed shall be
300 gallons.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2021 LBOWERS1 OUT TO CUSTOMER Completed