Permit Number: T21CM00756
Parcel: 136381510

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM00756
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

PROJECT: T21CM00756
7326 E Marigold Cir
Room Addition
Residential (1st Review)

TRANSMITTAL DATE: February 2, 2021

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin @tucsonaz.gov or (520) 837-4966
02/03/2021 SSHIELD1 ENGINEERING REVIEW Passed
02/03/2021 SSHIELD1 NPPO REVIEW Passed
02/17/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21CM00756

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with code compliance.

SITE PLAN:

Provide a site plan showing all buildings, R106.1.1. Show setback measurements to property lines and location of utility lines to the building. Update the extension square footage to 160 Sq.Ft.

FLOOR PLAN:

Provide a floor plan showing each room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH.

FRAMING PLAN:

Provide a roof framing plan showing truss or rafter location and sizes.

SECTIONS - DETAILS:

Provide structural details showing code compliant materials and fasteners from the foundation to the roof covering of new exterior walls. Include the wall to roof fastening.

ELECTRICAL PLANS:

Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.

Receptacle, lighting and smoke detector circuits require arc-fault protection, E3902.17.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details minimum (R-6 masonry walls and R-30 addition ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better.

If you have any questions, please contact: