Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM00660
Parcel: 106031050

Address:
3363 N STONE AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T21CM00660
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2021 PIMA COUNTY BUILDING-RESIDENTIAL REVIEW Approved
03/02/2021 STEVE SHIELDS ZONING REVIEW Approved
03/16/2021 SBLOOD1 ENGINEERING REVIEW Reqs Change Project: (T21CM00660)
Address: (3363 N STONE AV)
This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

5. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

6. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

7. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

8. Supporting Documentation Upload - Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

9. Sign the application and submit.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/17/2021 IMONSHI1 OUT TO CUSTOMER Completed