Permit Number: T21CM00659
Parcel: 13604818A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T21CM00659
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2021 JVINCEN1 FIRE REVIEW Approved
04/06/2021 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T21CM00659

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Drawing S2.2, Shear Wall Plan, shows Shear Walls SW1’s and SW2’s. Provide Details of these
Shear Walls.
2. 2. Drawing S4.2, Foundation Details, show Frame 1, Frame 2 and Frame 3 elevations. Locate these
on Plan. Also verify if it’s called Foundation Details correctly, make revisions as necessary.
3. 3. Drawing S4.2, Detail 123, 124 and 125, Side View shows Detail 209/S4.1, 208/S4.1, 207/S4.1,
127/S4.1. Provide these Details.
4. 4. Locate Sections 209/S5.1 and 212/S5.1 on Plan.
5. 5. Designer is to coordinate venting and drainage hole requirements for HSS tube members that are galvanized using
the hot-dip galvanizing process. Provide for plugs as needed.
AWS D-19.0 calls for welds on galvanized steel to be free of zinc. Field welds on galvanized parts requires the removal of the
zinc coating in the area of weld. Provide zinc paint (approved by the galvanizer) and apply as required to the weld and
steel area to provide protection.
6. Roof drainage and secondary drains are to comply with IBC 1502.1.

BUILDING REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
E0.1 ELECTRICAL ONE-LINE, SPECIFICATIONS, LEGENDS & NOTES: No electrical comments
E1.1 ELECTRICAL FLOOR PLAN & NOTES: No electrical comments
E1.2 ELECTRICAL ROOF PLAN & NOTES: No electrical comments
E2.1 ELECTRICAL LIGHTING PLAN & NOTES: No electrical comments
E3.1 ELECTRICAL SCHEDULE & CALCULATIONS: Either the Panel P1 or the TEP approved
meter can needs to provide circuit protection ie a 200 amp circuit breaker needs to be part of the design.
Usually, the design would rely upon a service rated panel (the panel would have a 200-amp service
rated CB) or the riser detail (E0.1) would show a CB as part of the meter disconnect. Cannot determine
if an approved TEP meter socket provides this circuit protection.

MECHANICAL REVIEW COMMENTS:
Approved

PLUMBING REVIEW COMMENTS:
Approved
04/06/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. The development package must be approved first.
2. Clearly show that primary roof drains are not directed to sidewalk surface.
04/06/2021 ROBERT SHERRY WATER REVIEW Completed
04/06/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM00659
8601 E Gold Links Rd
New Food Service

TRANSMITTAL: February 19, 2021
This site is located in the C-1 zone (UDC 4.7.20). Food Service is a permitted use in this zone (Table 4.8-4) Subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O

1. Zoning has reviewed the building plans for compliance with DP21-0004 and although it appears that the building plans match the DP the building plans cannot be approve until the DP is approved.

2. The development package sheets provided in the building plan set either need to be the stamped approved development package sheets, removed from the building plan set or mark as for reference only. If you elect to remove the development packs sheets or mark for reference only, ensure that sheet 6, Utility Plan, stays in the building set and is not marked for reference only.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
04/06/2021 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2021 IMONSHI1 OUT TO CUSTOMER Completed