Permit Number: T21CM00635
Parcel: 10308001S

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM00635
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet C-02 (Plan); Sheet C-06 (Detail 8): Detail 8 indicates a 7'-0" tall masonry wall, while the plan on Sheet C-02 indicates a new 8' high wall. A 7' wall does not require structural calculations, while the 8' wall does. Please coordinate.
2. General: Please provide a Special Inspections Certificate with Parts A and B completed.
3. General: Please provide written responses to all review comments.
03/16/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/17/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2021 IMONSHI1 OUT TO CUSTOMER Completed